Tashkent Mirzo-Ulugbek district, Durmon Yuli street 52
Online ground resistance detector/tester (mini-type, wired system)
Online ground resistance detector/tester (mini-type, wired system)
Online ground resistance detector/tester (mini-type, wired system)

Description

The online ground resistance detector developed by Sunlight does not change the structure of the original grounding system, and uses online monitoring technology such as non-contact measurement, which will not affect the grounding effect and normal operation of objects. There is no need for self-testing and real-time detection, and the product can be installed and used as a single product, or it can be formed into a wired network system or wireless network component system. With the support of the system, the data can be saved. Through the display of the accumulated data curve, you can intuitively see the changing trend of the grounding network and judge whether the grounding network is in good condition or not.

Protection class:

IP65 and WF2, can be used outdoors.

Power supply:

AC/DC 85~265V

Resistance range:

0.01Ω~200Ω

Resolution coefficient:

0.001Ω

Accuracy:

≤1Ω (error ≤10mΩ, 20℃±5℃, 70%RH below); ≤100Ω (error ≤±1%)

Working environment:

-40℃~85℃, humidity ≤95%RH (no condensation)

Overflow indication:

When the value is greater than 100Ω, the symbol “--” is displayed.

Alarm output:

The alarm on the panel and the indicator light are triggered at the same time; Dry contact (5A / 220V AC)

Communication interface:

RS485 (ModBUS RTU protocol), photoelectric isolation, 1200m / 9600bps

Product dimensions:

169mm×142mm×150mm

Grounding wire perforation dimensions:

54mm×21mm, closed type (can pass through 54mm×10mm flat steel or Ф20mm cable)

Installation:

The grounding wire passes through the central hole of the detector and is fixed to the ground with a flat steel plate.